Universal Cutout Cover CT-D02
- Cover for most < 27kV porcelain and polymer non-loadbreak cutouts including Chance type C, AlumaForm, ABB,Cooper/Eaton Type L cutouts
- Neck clip adjusts to the size of the cutout for a tight and secure fit
- Easiest hotstick install in the industry
- No locking pins
Installation // Hotstick
Adjustable Neck Demo
Product Description
This Universal Cutout Cover with adjustable snap-lock clip provides a tight fit on most 15-27kV distribution cutouts without any locking pins. The clip keeps the cover secure while its unique shape fully covers arcing horns to prevent electrocution events as well as the top portion of the cutout, allowing insulator skirts to naturally clean. Plus, enjoy a safer installation and zero system downtime when installed via hotstick.
Additional Information
Cutout Application | < 27 kV Polymer Cutouts, < 27 kV Porcelain Cutouts |
---|---|
Flame Retardant Rating | V-0 |
Hotstick Friendly | Yes |
Hotstick Installation Tool | No additional tool needed |
Material | PLS-PP-FR-UV |
Package Quantity | 20 |
Voltage Rating (up to) | 35 kV |
Wind Resistance Rating | 120 mph |
Tests |
Results |
IEEE 1656 / 5.2 Wet Withstand |
>18 kV |
IEEE 1656 / 5.3 Wet power frequency flashover |
>95% |
IEEE 1656 / 5.4 Lightning Impulse withstand |
125kV |
IEEE 1656 / 5.5 Cold temperature test |
Passed / -25C |
IEEE 1656 / 5.6 Ultraviolet Aging |
5,000 hours |
Wind Retention |
>90 mph |
UL 94 Flammability of Plastic Materials |
V-0 |
Properties |
Results |
ASTM D149 Dielectric strength |
467 V/mil (18.4 kV/mm) |
ASTM D2303 Inclined plane tracking and erosion: Initial Tracking (variable voltage) |
4.0 kV |
ASTM D638 Tensile Strength @ Yield |
2,400 psi (17 MPa) |
ASTM D790 Flexural Modulus |
140,000 psi (966 Mpa) |
Regulatory |
ROHS Compliant |
Similar Products
You may also like…
-
Universal Small Equipment & Bushing Cover BC-D01
Cover for most distribution equipment with a shed diameter < 4"
-
Universal Medium Equipment & Bushing Cover BC-D02
Cover for primarily anything larger than a standard transformer bushing, with a shed diameter < 5.5"
-
Universal Loadbreak Cutout Cover CT-D04
Loadbreak cutout cover for most distribution loadbreak cutouts, including ABB, Hubbell-Chance, AlumaForm, and MacLean loadbreak cutouts
-
Insulating Fusing Tape FTP-200
Self-fusing silicone tape